产品展示|Products

C7076A1007/U霍尼韦尔火焰探测器

 


C7076A1007/U
Adjustable Sensitivity Ultraviolet Flame Detector
Overview
Solid state dynamic self check flame detectors for use with BC7000, R4140 or FSP5075 with R7476 Amplifier and 7800 SERIES with R7886 Amplifier.

Features

•Use Honeywell Flame Safeguard primary safety controls requiring adjustable sensitivity ultraviolet flame detection.
•Detect ultraviolet radiation from flames.
•Include dual sensitivity adjustment.
•C7076A meets NEMA 4 standards with viewing window rated to 20 psi.
•C7076D has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi.

Product Specifications
ApplicationGas fired burners; Oil fired burnersDimensions (in.)4 in. high x 4 in. wide x 10 1/4 in. deepDimensions (mm)102 mm high x 102 mm wide x 261 mm deepUsed WithFlame Amplifiers: R7476, R7886Weight (lb)6.6 lbWeight (kg)3 kgCommentsDynamic self-checking flame detector with adjustable sensitivityMounting1 in. NPTElectrical Ratings120 VacFrequency60 HzApprovals, Underwriters Laboratories Inc.Listed: File No. MP268, Guide No. MCCZApprovals, Canadian Standards AssociationCertified: Master Report LR1620Electrical ConnectionsTerminal blockPower Consumption7.0 WVibration0.5 G maxApprovals, Swiss REAcceptableApprovals, Factory MutualApproved: Report No. FM26980TypeUltraviolet, Adjustable SensitivityAmbient Temperature Range (F)-40 F to +160 FAmbient Temperature Range (C)-40 C to +71 CNEMA RatingNEMA 4

 

 